TECHNICAL DATA  ::   
 

 

Inside Diameter (ID)
of Metal Pipe

Line Temp.
+7°C (+44.6°F)

Line Temp.
+2°C (+35.6°F)
Line Temp.
-8°C (+17.6°F)
Line Temp.
-18°C (-0.4°F)
Line Temp.
-3°C (-22°F)
Inside Diameter
ID  9 mm. thru 75 mm.
ID over 75 mm.
Base on Mild Condition, Max Ambient Temp. 25°C (77°F), 50% RH

6 mm.
9 mm.

9 mm.
13 mm.
13 mm.
13 mm.
19 mm.
19 mm.
25 mm.
25 mm.
Inside Diameter
ID   9 mm. thru  25 mm.  
ID 26 mm. thru 50 mm.   
ID 51 mm. thru 75 mm.
ID 76 mm. upward
Base on Normal Condition, Max Ambient Temp. 30°C (86°F), 70% RH
13 mm.
13 mm.
13 mm.
13 mm.
13 mm.
19 mm.
19 mm.
19 mm.
19 mm.
19 mm.
25 mm.
25 mm.
25 mm.
25 mm.
25 mm.
32 mm.
32 mm.
32 mm.
32 mm.
38 mm.
Inside Diameter
ID     9 mm. thru    25 mm.  
ID   26 mm. thru    50 mm.   
ID   51 mm. thru    75 mm.
ID   76 mm. thru  100 mm.
ID 101 mm. thru  250 mm.
ID 251 mm. upward
Base on Severe Condition, Max Ambient Temp 33°C (91.4°F), 80% RH
19 mm.
25 mm.
25 mm.
25 mm.
28 mm.
28 mm.
25 mm.
25 mm.
25 mm.
28 mm.
28 mm.
32 mm.
32 mm.
32 mm.
38 mm.
38 mm.
44 mm.
44 mm.
38 mm.
38 mm.
38 mm.
44 mm.
44 mm.
50 mm.
38 mm.
50 mm.
50 mm.
56 mm.
56 mm.
63 mm.
Inside Diameter
ID    9 mm.  thru   25 mm.  
ID   26 mm. thru   50 mm.   
ID   51 mm. thru   75 mm.
ID   76 mm. thru 100 mm.
ID 101 mm. thru 250 mm.
ID 251 mm. upward
On Extremely Severe Condition, Max Ambient Temp 33°C (91.4°F), 85% RH
25 mm.
28 mm.
32 mm.
32 mm.
38 mm.
38 mm.
32 mm.
32 mm.
32 mm.
38 mm.
38 mm.
38 mm.
38 mm.
44 mm.
44 mm.
50 mm.
56 mm.
56 mm.
50 mm.
50 mm.
50 mm.
59 mm.
63 mm.
63 mm.
50 mm.
56 mm.
63 mm.
69 mm.
81 mm.
88 mm.

        For Air-Ducting System

       
 Thickness Recommendation for Air-Ducting System

Ambient Condition

Operating Temperature ( Cool Air Temperature )

+15°C (+59.0°F)

+13°C (+55.4°F)
+10°C (+50.0°F)
+7°C (+44.6°F)
+5°C (+41.0°F)
27°C (80.6°F), 50% RH
 6 mm .
 6 mm.
 6 mm.
 9 mm.
 9 mm.
30°C (86.0°F), 70% RH
 9 mm.
 9 mm.
 9 mm.
13 mm.
16 mm.
32°C (89.6°F), 80% RH
16 mm.
19 mm.
19 mm.
25 mm.
28 mm.
34°C (93.2°F), 85% RH
25mm.
25 mm.
25 mm.
32 mm.
38 mm.

 

             

 

          
           In areas of low relative humidity, insulation thickness 6mm. will be sufficient for            condensation control purpose.  However, we would recommend a minimum
           thickness of 9mm. in order to significantly reduce the heat gain from outer
           sources.    


          
For chilled water piping and refrigeration

          Thickness Recommendation for Chilled Water Piping and Refrigeration

     











   






 